FREE SHIPPING ON ALL ORDERS OVER $300

APC Galaxy VS uninterruptible power supply (UPS) Double-conversion (Online) 40 kVA 40000 W

SKU
GVSUPS40KR0B5HS
-39%
Special Price $28,962.56 Regular Price $47,393.28
Out of stock
40kW 400V with N+1 power module, for 5 smart modular 9Ah battery strings, Start-up 5x8
Highly efficient, easy-to-deploy 40kW, 400V 3-phase UPS that brings best-in-class power protection and low total cost of ownership to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. This UPS is for up to 5 smart modular high capacity battery strings, but is supplied without batteries, so you can easily customize the battery runtime. Includes 5x8 start-up service and one additional power module for N+1 redundancy.

Compatible with Schneider Electric's lithium ion battery solution
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability.

Built-in backfeed protection
Full built-in backfeed contactor ensures that no electricity is sent back to the grid.

Parallel-redundant capable
Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy

Parallel-capacity capable
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.

Flexible DC bus
Optimizes battery sizing and supports a wide range of energy storage technologies, including VRLA, Li-ion, and NiCd batteries.

Embedded Network Management Card
Allows you to remotely manage alert thresholds and monitor your UPS over EcoStruxure IT, Web, SNMP, or Modbus TCP and Modbus RTU.

Compact UPS
High-density technology and full front access make this UPS a footprint saver well suited for confined spaces.

High efficiency in double conversion mode
Consistently high power quality at high efficiency, even at low load levels. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.

ECOnversion mode
Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.

Robust operation
No power derating in kW up to 40 degrees C or 104 degrees F.

Input Power Factor Correction
Minimizes installation costs by enabling the use of smaller generators and cabling.

Wide input voltage range
Designed for harsh electrical environments to save battery life.

Modular UPS design
Provides design redundancy and fast serviceability with improved mean time to repair, via self-diagnosing, field-replaceable modules.

Multiple levels of service offers
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like Schneider Electric to do for you.

EcoStruxure IT Expert
From your smartphone or computer, connect to our cloud-based, do-it-yourself monitoring system that collects, organizes, and distributes critical alerts and key information in real time, providing a unified view of even highly distributed physical infrastructure environments. Optimize your uptime and maintenance planning, and anticipate infrastructure issues before they occur with advanced analytics and performance benchmarking. Available in select countries.

Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
SKU GVSUPS40KR0B5HS
EAN 0731304410133
Specification
Power
Output frequency50/60 Hz
Output power capacity40 kVA
Output power40000 W
Input operation voltage (min)340 V
Input operation voltage (max)460 V
Output operation voltage (min)380 V
Output operation voltage (max)415 V
Maximum current72 A
Output voltage Total Harmonic Distortion (THD)3%
Output voltage regulation1%
Input power factor0.99
Input current Total Harmonic Distortion (THD)3%
Crest factor2.5:1
ECO modeYes
Input frequency40/70 Hz
Performance
UPS topologyDouble-conversion (Online)
Number of input phases3
Response time3 ms
WaveformSine
Noise level65 dB
Audible alarm(s)Yes
Features
Output frequency50/60 Hz
UPS topologyDouble-conversion (Online)
Output power capacity40 kVA
Number of input phases3
Response time3 ms
Output power40000 W
Input operation voltage (min)340 V
Input operation voltage (max)460 V
Output operation voltage (min)380 V
Output operation voltage (max)415 V
Maximum current72 A
WaveformSine
Output voltage Total Harmonic Distortion (THD)3%
Output voltage regulation1%
Input power factor0.99
Input current Total Harmonic Distortion (THD)3%
Crest factor2.5:1
Noise level65 dB
Audible alarm(s)Yes
ECO modeYes
Input frequency40/70 Hz
Battery
Battery technologySealed Lead Acid (VRLA)
Battery voltage480 V
Design
Form factorTower
Product colourWhite
International Protection (IP) codeIP20
CertificationIEC 62040-1-1, IEC 62040-2, OSHPD
Display typeLCD
Operational conditions
Operating temperature (T-T)0 - 40 °C
Storage temperature (T-T)-15 - 40 °C
Operating relative humidity (H-H)0 - 95%
Operating altitude0 - 1005.8 m
Non-operating altitude0 - 3048 m
Technical details
Output frequency50/60 Hz
Harmonized System (HS) code85078000
Weight & dimensions
Width550 mm
Depth847 mm
Height1970 mm
Weight250 kg
Package width755 mm
Package depth1010 mm
Package height2082 mm
Package weight250 kg
Packaging data
ManualYes
Package width755 mm
Package depth1010 mm
Package height2082 mm
Package weight250 kg
Logistics data
Harmonized System (HS) code85078000
Certificates
CertificationIEC 62040-1-1, IEC 62040-2, OSHPD
Packaging content
ManualYes
Manufacturer APC
PDF Url https://objects.icecat.biz/objects/
In Stock N